SUPERSERVER 5010H/5010E
USER’S MANUAL
Revision 1.1
Vue de la page 0
1 2 3 4 5 6 ... 127 128

Résumé du contenu

Page 1 - SUPER

® SUPERSuperServer 5010HSuperServer 5010HSuperServer 5010HSuperServer 5010HSuperServer 5010HSuperServer 5010ESuperServer 5010ESuperServer 5010ESuper

Page 2

NotesSUPERSERVER 5010H/5010E User's Manualx

Page 3 - Manual Organization

SUPERSERVER 5010H/5010E User's Manual7-28BIOS7-7 Power SetupChoose Power Setup from the AMIBIOS Setup main menu. All Power Setupoptions are desc

Page 4

Chapter 7: AMIBIOS7-29BIOSACPI Aware O/SThis option allows the system to utilize Intel's ACPI (Advanced Configurationand Power Interface) specifi

Page 5 - Manual Or

SUPERSERVER 5010H/5010E User's Manual7-30BIOSAfter G3 EnableThis option allows AfterG3 Enable support. The settings are Disabled andEnabled. Di

Page 6 - Chapter 3: System Interface

Chapter 7: AMIBIOS7-31BIOSGreen PC Monitor Power StateThis option specifies the power state that a green PC-compliant monitorenters when BIOS places i

Page 7 - Chapter 4: System Safety

SUPERSERVER 5010H/5010E User's Manual7-32BIOSTHRM Throttle RatioTHRM throttling is used to lower power consumption and reduce heat. Thesettings

Page 8 - Chapter 7: BIOS

Chapter 7: AMIBIOS7-33BIOSRTC ResumeThis allows you to direct the system to resume operation at a predeterminedtime by using the real-time clock. The

Page 9 - Appendices:

SUPERSERVER 5010H/5010E User's Manual7-34BIOS7-8 Boot SetupChoose Boot Setup from the AMIBIOS Setup main menu. All Boot Setupoptions are describ

Page 10

Chapter 7: AMIBIOS7-35BIOS2nd Boot DeviceThe settings for the 2nd Boot Device are Removeable Device, Hard Drive,ATAPI CDROM, Onboard LAN1Option and On

Page 11 - Chapter 1

SUPERSERVER 5010H/5010E User's Manual7-36BIOS7-9 Security SetupChoose Security Setup from the AMIBIOS Setup main menu. All SecuritySetup options

Page 12 - Control Panel

Chapter 7: AMIBIOS7-37BIOSChange Supervisor PasswordThis option allows you to change a supervisor password that was enteredpreviously.Change User Pass

Page 13 - Rear I/O Panel

Chapter 1Introduction to the SuperServer 5010H/5010E1-1 OverviewThe Supermicro SuperServer 5010H/5010E is a high-end single processor,1U rackmount ser

Page 14 - Chipset Overview

SUPERSERVER 5010H/5010E User's Manual7-38BIOS7-10 Exit SetupChoose Exit Setup from the AMIBIOS Setup main menu. All Exit Setup op-tions are desc

Page 15 - PCI Expansion Slots

Chapter 7: AMIBIOS7-39BIOSLoad Optimal DefaultsHighlighting this setting and then pressing <Enter> provides the optimumperformance settings for

Page 16 - Other Features

SUPERSERVER 5010H/5010E User's Manual7-40BIOS Notes

Page 17 - Asia-Pacific

Appendix ABIOS Error Beep Codes & MessagesDuring the POST (Power-On Self-Test) routines, which are performedeach time the system is powered on, er

Page 18

SUPERSERVER 5010H/5010E ManualA-2AMI BIOS Error Beep CodesBeep Code Error Message Description 1 beep Refresh The memory refresh circuitry on the mot

Page 19 - Server Installation

B-1Appendix B: AMIBIOS POST Checkpoint Codes Appendix BAMIBIOS POST Checkpoint CodesWhen AMIBIOS performs the Power On Self Test, it writes dia

Page 20 - Server Precautions:

SUPERSERVER 5010H/5010E ManualB-2B-2 Bootblock Recovery CodesThe bootblock recovery checkpoint codes are listed in order of execution:Checkpoint Code

Page 21

B-3Appendix B: AMIBIOS POST Checkpoint CodesB-3 Uncompressed Initialization CodesThe following runtime checkpoint codes are listed in order of executi

Page 22 - Installing the Rack Rails:

SUPERSERVER 5010H/5010E ManualB-4Checkpoint Code Description25h Interrupt vector initialization is done. Clearing the password if thePOST DIAG switch

Page 23

B-5Appendix B: AMIBIOS POST Checkpoint CodesCheckpoint Code Description4Bh The amount of memory above 1 MB has been found and verified. Checkingfor a

Page 24

SUPERSERVER 5010H/5010E Manual1-21-2 Server Chassis FeaturesThe SuperServer 5010H/5010E is a high-end, scaleable 1U rackmountserver platform designed

Page 25

SUPERSERVER 5010H/5010E ManualB-6Checkpoint Code Description60h The DMA page register test passed. Performing the DMA Controller 1base register test n

Page 26 - (with SCSI Installed)

B-7Appendix B: AMIBIOS POST Checkpoint CodesCheckpoint Code Description89h The programming after WINBIOS Setup has completed. Displaying thepower on s

Page 27 - (with IDE Installed)

SUPERSERVER 5010H/5010E ManualB-8Checkpoint Code Description9Bh Returned after setting the RS-232 base address. Performing any requiredinitialization

Page 28

B-9Appendix B: AMIBIOS POST Checkpoint CodesB-4 Bus Checkpoint CodesThe system BIOS passes control to different buses at the following checkpoints:Che

Page 29

SUPERSERVER 5010H/5010E ManualB-10Notes

Page 30

C-1Appendix C: List of FiguresAppendix CList of FiguresDescription Page I/O Shield 1-3 Identifying the Sections of the Rack Rails 2-3 Install

Page 31 - System Interface

SUPERSERVER 5010H/5010E ManualC-2Notes

Page 32 - 3-3 Control Panel LEDs

D-1Appendix D: System SpecificationsAppendix DSystem SpecificationsProcessorsOne 370-pin Intel Pentium III FCPGA 600 MHz - 1 GHz or a CeleronFCPGA/PP

Page 33 - 3-6 Motherboard LEDs

SUPERSERVER 5010H/5010E ManualD-2PCI Expansion SlotOne (1) onboard 32-bit 33 MHz (5V) PCI slot (*Default-- bundled witha 32-bit 33 MHz 5V Riser Card)

Page 34

1-3Chapter 1: IntroductionThe SC810 is a 1U rackmount chassis. Its I/O panel provides one mother-board expansion slot, one COM port (the other is int

Page 35 - System Safety

SUPERSERVER 5010H/5010E Manual1-41-3 Mainboard FeaturesAt the heart of the SuperServer 5010H/5010E lies the 370SSR+/370SSE+, asingle processor motherb

Page 36

1-5Chapter 1: IntroductionNumber Generator (RNG) for stronger encryption, digital signing and secu-rity protocols. The FWH stores the system BIOS and

Page 37 - 4-3 ESD Precautions

SUPERSERVER 5010H/5010E Manual1-6Onboard Controllers/PortsAn onboard IDE controller supports one floppy drive and up to fourUDMA/100 hard drives or AT

Page 38

1-7Chapter 1: Introduction1-4 CONTACTING SUPERMICROHeadquartersAddress: Super Micro Computer, Inc.980 Rock Ave.San Jose, CA 95131 U.S.A.Tel: +1 (408)

Page 39 - Precautions

SUPERSERVER 5010H/5010E Manual1-8NOTES

Page 40 - Unpacking

Chapter 2: Server Installation2-1Chapter 2 Server Installation2-1 OverviewThis chapter provides a quick setup checklist to get your SuperServer

Page 41 - Connecting Power Cables

The information in this User’s Manual has been carefully reviewed and is believed to beaccurate. The vendor assumes no responsibility for any inaccur

Page 42 - Connecting the Control Panel

2-2SUPERSERVER 5010H/5010E ManualChoosing a Setup Location:- Leave enough clearance in front of the rack to enable you to open the front door comp

Page 43 - 5-4 I/O Ports

Chapter 2: Server Installation2-32-4 Installing the SuperServer 5010H/5010E into aRackThis section provides information on installing the SuperServer

Page 44

2-4SUPERSERVER 5010H/5010E ManualInstalling the Chassis Rails:Position the fixed chassis rail sections you just removed along the side ofthe 5010H/501

Page 45 - 5-6 Installing Memory

Chapter 2: Server Installation2-5Figure 2-3. Installing the Server into a RackInstalling the Server into the Rack:You should now have rails attached

Page 46 - 5-7 Adding PCI Cards

2-6SUPERSERVER 5010H/5010E ManualFigure 2-4. Installing the Server into a Telco RackInstalling the Server into a Telco Rack:If you are installing th

Page 47 - 370SSE+ Motherboard

Chapter 2: Server Installation2-72-5 Checking the Motherboard SetupAfter you install the 5010H/5010E in the rack, you will need to open the unitto mak

Page 48 - SUPER 370SSR+

2-8SUPERSERVER 5010H/5010E ManualPower SupplyCover RecessCover ReleaseButtonsTop Chassis Cover (Removed)PCI Riser CardRetention RailAir Seal (*See not

Page 49

Chapter 2: Server Installation2-9SystemMemoryBlower FanFloppy DriveCD-ROM DriveControl PanelIDE Drive5010EFigure 2-5B. Accessing the Inside of the Su

Page 50 - SUPER 370SSE+

2-10SUPERSERVER 5010H/5010E Manual6. Check all cable connections and airflow:Make sure all power and data cables are properly connected and notblockin

Page 51

Chapter 2: Server Installation2-115. Supplying power to the system:The last thing you must do is to provide input power to the system. Plugthe power

Page 52 - 5-8 Connector Definitions

PrefaceAbout This ManualThis manual is written for professional system integrators and PC techni-cians. It provides information for the installation

Page 53 - Power LED

2-12SUPERSERVER 5010H/5010E ManualNotes

Page 54 - Overheat LED (JOH)

Chapter 3: System Interface3-1Chapter 3System Interface3-1 OverviewThere are several LEDs on the control panel as well as others on the SCSIdrive carr

Page 55 - Universal Serial Bus (USB)

SUPERSERVER 5010H/5010E Manual3-23-3 Control Panel LEDsThe control panel located on the front of the SC810 chassis has five LEDs.These LEDs provide yo

Page 56 - LAN1/LAN2 Ports

Chapter 3: System Interface3-3l Power: Indicates power is being supplied to the system's powersupply units. This LED should normally be illumin

Page 57 - Wake-On-LAN

SUPERSERVER 5010H/5010E Manual3-4l DA1 (SCSI LED) Indicator (5010H only) DA1 (SCSI LED) Indicator (5010H only) DA1 (SCSI LED) Indicator (5010H only

Page 58 - Connector

Chapter 4: System Safety4-1 Chapter 4System Safety4-1 Electrical Safety Precautions!Basic electrical safety precautions should be followed to prote

Page 59 - Onboard LAN Enable/

SUPERSERVER 5010H/5010E Manual4-24-2 General Safety PrecautionsFollow these rules to ensure general safety:l Keep the area around the SuperServer 501

Page 60

Chapter 4: System Safety4-34-3 ESD PrecautionsElectrostatic discharge (ESD) is generated by two objects withdifferent electrical charges coming into c

Page 61 - Floppy Connector

SUPERSERVER 5010H/5010E Manual4-4Notes

Page 62 - Connectors

Chapter 5: Advanced Motherboard Setup5-1 Chapter 5Advanced Motherboard SetupThis chapter covers the steps required to install the 370SSR+/370SSE+moth

Page 63

SUPERSERVER 5010H/5010E ManualivChapter 4: System SafetyYou should thoroughly familiarize yourself with this chapter for a generaloverview of safety

Page 64 - 6-2 Control Panel

5-2SUPERSERVER 5010H/5010E Manual5-2 Motherboard InstallationThis section explains the first step of physically mounting the 370SSR+(5010H), 370SSE+(5

Page 65 - Replacing System Cooling Fans

Chapter 5: Advanced Motherboard Setup5-35-3 Connecting CablesNow that the motherboard is installed, the next step is to connect the cablesto the board

Page 66 - Accessing the Drive Bays

5-4SUPERSERVER 5010H/5010E ManualConnecting the Control PanelJF1 contains header pins for various front control panel connectors.See Figure 5-1 for th

Page 67

Chapter 5: Advanced Motherboard Setup5-55-5 Installing ProcessorsAvoid placing direct pressure to the top of the processor package. Always connect th

Page 68

5-6SUPERSERVER 5010H/5010E Manual2. Attaching heat sinks to the processors:One passive heat sink has been included with your SuperServer 5010H/5010E.

Page 69

Chapter 5: Advanced Motherboard Setup5-75-6 Installing Memory1. Memory support:The 370SSR+/SSE+ supports 64MB/128MB/256MB/512 MB unbufferedSDRAM in th

Page 70 - Replacing the Power Supply

5-8SUPERSERVER 5010H/5010E Manual5-7 Adding PCI Cards1. 32-bit PCI slot:The 370SSR+/370SSE+ has one 32-bit MHz 5V PCI slot available. A risercard des

Page 71

Chapter 5: Advanced Motherboard Setup5-9Figure 5-6. Adding PCI CardsCPU SocketPCI Riser CardMemory ModulesFigure 5-5. 5V, 32-bit 33 MHz Riser Card3

Page 72

5-10SUPERSERVER 5010H/5010E ManualCOM1J30KB/MOUSEATX POWER J39 J38J32, J33USBCPU FANDIMM0DIMM1PCI 1PCI 2PCI 3 JF1 IR J19FLOPPY IDE2 IDE1 J18

Page 73 - Chapter 4

Chapter 5: Advanced Motherboard Setup5-11370SSR+ Quick Reference (for 5010H)Jumpers Description Default SettingJBT1 CMOS Clear Pins 1-2 (Normal)JP11/1

Page 74 - 7-3 Running Setup

vManual OrganizationIntroductionChp1Installation SystemInterfaceSystemSafetyMotherboardDetailsChassisDetailsBIOS andSetup RoutineChp3Chp2Chp5Chp4Chp6A

Page 75 - The Main BIOS Setup Menu

5-12SUPERSERVER 5010H/5010E ManualCOM1J30KB/MOUSEATX POWER J39 J38J32, J33USBCPU FANDIMM0DIMM1PCI 1PCI 2PCI 3 JF1 IR J19FLOPPY IDE2 IDE1 J18

Page 76 - 7-4 Advanced Chipset Setup

Chapter 5: Advanced Motherboard Setup5-13370SSE+ Quick Reference (5010E only)Jumpers Description Default SettingJP11/12 Front Side Bus Speed Both: Pin

Page 77

5-14SUPERSERVER 5010H/5010E Manual5-8 Connector DefinitionsPower Supply ConnectorThe primary power supply connec-tor on the 370SSR+/370SSE+ isdesignat

Page 78 - Super IO Configuration

Chapter 5: Advanced Motherboard Setup5-15 HDD LED PinDefinitions(JF1)PinNumber1314Definition+5vHD ActiveHDD LEDThe Hard Disk Drive LED connec-tion is

Page 79

5-16SUPERSERVER 5010H/5010E ManualResetThe Reset connection is locatedon pins 3 and 4 of JF1. This con-nector attaches to the Reset but-ton on the co

Page 80 - IDE Configuration

Chapter 5: Advanced Motherboard Setup5-17Serial PortsSerial connector COM1 is locatedbeside the VGA port (see Figure5-8). COM2 is a header locatedbeh

Page 81

5-18SUPERSERVER 5010H/5010E ManualATX PS/2 Keyboard andPS/2 Mouse PortsThe ATX PS/2 keyboard and thePS/2 mouse are located on J30.See the table on the

Page 82

Chapter 5: Advanced Motherboard Setup5-19Wake-On-RingThe Wake-on-Ring (JWOR) headerallows your computer to receiveand be "woken up" by an in

Page 83 - Floppy Configuration

5-20SUPERSERVER 5010H/5010E Manual5-9 Jumper SettingsExplanation ofJumpersTo modify the operation of themotherboard, jumpers can be usedto choose betw

Page 84 - Boot Settings Configuration

Chapter 5: Advanced Motherboard Setup5-21CMOS ClearRefer to the table on the right forsetting JBT1 to clear CMOS. Al-ways remove the AC power cordfro

Page 85

SUPERSERVER 5010H/5010E ManualviTable of ContentsPrefaceAbout This Manual ...

Page 86

5-22SUPERSERVER 5010H/5010E ManualJumperPositionOpenClosedDefinitionEnabledDisabledLVD CH A SCSITerminationJumper Settings (JPA1)LVD Channel A SCSI Te

Page 87 - Event Log Configuration

Chapter 5: Advanced Motherboard Setup5-23IDE ConnectorsThere are no jumpers to config-ure the onboard IDE connectorsJ18 and J19. Refer to the tableon

Page 88 - GMCH Configuration

5-24SUPERSERVER 5010H/5010E ManualSignal Names+DB(12)+DB(13)+DB(14)+DB(15)+DB(P1)+DB(0)+DB(1)+DB(2)+DB(3)+DB(4)+DB(5)+DB(6)+DB(7)+DB(P)GROUNDDIFFSENST

Page 89

Chapter 6: Advanced Chassis Setup6-1Chapter 6Advanced Chassis SetupThis chapter covers the steps required to install components and performmaintenance

Page 90

6-2SUPERSERVER 5010H/5010E ManualUPERSRSUPERRFigure 6-2. Chassis Rear View6-2 Control PanelThe control panel (located on the front of the chassis) m

Page 91

Chapter 6: Advanced Chassis Setup6-36-3 System FansOne 10-cm blower fan provides all the cooling needed for the Super-Server 5010H/5010E. An optional

Page 92 - ICH2 Configuration

6-4SUPERSERVER 5010H/5010E ManualFigure 6-3. System Cooling Fans6-4 Drive Bay Installation/RemovalAccessing the Drive BaysSCSI Drives: You do not nee

Page 93

Chapter 6: Advanced Chassis Setup6-5SCSI Drive Installation (5010H only)1. Mounting a SCSI drive in a drive carrier:The SCSI drives are mounted in dri

Page 94 - The settings for

6-6SUPERSERVER 5010H/5010E ManualFigure 6-5. Removing SCSI Drives (5010H)2. Installing/removing hot-swap SCSI drives:Two SCSI drive bays are located

Page 95

Chapter 6: Advanced Chassis Setup6-7SCSI Power CablesSCSI power cables should be routed so that they do not block the airflowthrough the chassis. The

Page 96 - 7-6 PCI PnP Setup

Power ... 3-33-4 SCSI Drive Carrier LEDs (5010H).

Page 97

6-8SUPERSERVER 5010H/5010E Manual6-5 Power SupplyThe SuperServer 5010H/5010E has a single 200 watt power supply. Thispower supply has an auto-switchi

Page 98

Chapter 6: Advanced Chassis Setup6-9Figure 6-6. Chassis Rear ViewExternal High Density SCSII/O Ports (seeFigure 1.1)Connector(5010H only)5010E5010HPC

Page 99

6-10SUPERSERVER 5010H/5010E ManualNotes

Page 100 - 7-7 Power Setup

Chapter 7: AMIBIOS7-1BIOSChapter 4BIOS7-1 IntroductionThis chapter describes the AMIBIOS for the 5010H/5010E. The AMI ROMBIOS is stored in a Flash EE

Page 101

SUPERSERVER 5010H/5010E User's Manual7-2BIOS7-2 BIOS Features• Supports Plug and Play V1.0A and DMI 2.3• Supports Intel PCI (Peripheral Component

Page 102

Chapter 7: AMIBIOS7-3BIOS Use the Up/Down arrow keys or the <Tab> key to move between the differentsettings in the above menu. When the items &q

Page 103

SUPERSERVER 5010H/5010E User's Manual7-4BIOS Use the Up/Down arrow keys to select the "Health Monitor Features" line.When the "Hea

Page 104

Chapter 7: AMIBIOS7-5BIOSCPU Overheat WarningThis option allows you to Enable or Disable a system overheat warningsignal, used to notify you in the ev

Page 105

SUPERSERVER 5010H/5010E User's Manual7-6BIOSThe Super IO Configuration includes the following items:Serial Port 1 AddressThis option specifies th

Page 106 - Boot Device Priority

Chapter 7: AMIBIOS7-7BIOSParallel Port IRQThis option allows the user to set the Parallel Port IRQ. The settingsfor this item include 5 and 7.Parallel

Page 107 - ATAPI CDROM Drives

SUPERSERVER 5010H/5010E ManualviiiWake-On-LAN ... 5-195-9 Jumper

Page 108 - User Password

SUPERSERVER 5010H/5010E User's Manual7-8BIOSIDE ConfigurationOnboard PCI IDE ControllerThis option allows the user to enable or disable the integ

Page 109 - Change Supervisor Password

Chapter 7: AMIBIOS7-9BIOSTypeThis option sets the type of device that the AMIBIOS attemptsto boot from after AMIBIOS POST is completed. The settingsin

Page 110 - Exit Discarding Changes

SUPERSERVER 5010H/5010E User's Manual7-10BIOStect the DMA Mode. Select SWDMA0 through SWDMA2 toset single word DMA0 through DMA2. Select MWDMA0

Page 111 - Discard Changes

Chapter 7: AMIBIOS7-11BIOSATA(PI) 80Pin Cable DetectionThis option selects the mechanism for detecting the 80-pin ATA(PI) cable.Options include Host a

Page 112 - Notes

SUPERSERVER 5010H/5010E User's Manual7-12BIOSBootUp Num LockThis option is used to select the status of the Number Lock function on yourkeyboard

Page 113 - Appendix A

Chapter 7: AMIBIOS7-13BIOSSystem KeyboardThis option is to let the system know if a keyboard is Present or Absent.Primary DisplayThis option specifies

Page 114 - AMI BIOS Error Beep Codes

SUPERSERVER 5010H/5010E User's Manual7-14BIOSbe used to slow the computer system down or to troubleshoot error mes-sages. Write-Thru: This optio

Page 115 - AMIBIOS POST Checkpoint Codes

Chapter 7: AMIBIOS7-15BIOSEvent Log ConfigurationEvent LoggingThis option Enables or Disables the logging of events. You can use thisscreen to select

Page 116 - B-2 Bootblock Recovery Codes

SUPERSERVER 5010H/5010E User's Manual7-16BIOS7-5 Chipset SetupChoose Chipset Setup from the AMIBIOS Setup Utility main menu. The screenis shown b

Page 117

Chapter 7: AMIBIOS7-17BIOSInternal Graphics Mode SelectThis option selects the mode for the internal graphics mode. Settings in-clude Disabled, Enabl

Page 118 - Hit <DEL>

Table of ContentsixEvent Log Configuration ... 7-157-5 Chipset Setup ...

Page 119 - <WAIT...>

SUPERSERVER 5010H/5010E User's Manual7-18BIOSInit Display Cache MemoryThis option allows the Initial Display cache memory to be adjusted. Thesett

Page 120

Chapter 7: AMIBIOS7-19BIOSSystem Memory FrequencyThis option allows the system memory frequency to be adjusted. The set-tings are 100 MHz (for PC100

Page 121

SUPERSERVER 5010H/5010E User's Manual7-20BIOSICH2 ConfigurationYou can use this screen to select options for the ICH2 Configuration. Usethe up a

Page 122

Chapter 7: AMIBIOS7-21BIOSSMBus ControllerThe settings for this option are Enabled and Disabled.LPC 4Eh-4Fh DecodeThis option allows the LPC 4Eh-4Fh t

Page 123 - B-4 Bus Checkpoint Codes

SUPERSERVER 5010H/5010E User's Manual7-22BIOSProcessor Serial NumberIntel includes a serial number in their processors to act as a unique systemi

Page 124 - UPERSERVER 5010H/5010E Manual

Chapter 7: AMIBIOS7-23BIOSC000, 16k ShadowC400, 16k ShadowC800, 16k ShadowCC00, 16k ShadowD000, 16k ShadowD400, 16k ShadowD800, 16k ShadowDC00, 16k Sh

Page 125 - List of Figures

SUPERSERVER 5010H/5010E User's Manual7-24BIOSPlug & Play OSChoose the No setting for computers that do not meet the Plug and Playspecificatio

Page 126

Chapter 7: AMIBIOS7-25BIOSPCI Latency TimerThis option specifies the latency timing of the PCI clocks for all PCI devices.Settings include 32, 64, 96,

Page 127 - System Specifications

SUPERSERVER 5010H/5010E User's Manual7-26BIOSLegacy USB SupportThis option allows Legacy USB support. The settings are Disabled, En-abled and Au

Page 128

Chapter 7: AMIBIOS7-27BIOSDMA Channel 0DMA Channel 1DMA Channel 3DMA Channel 5DMA Channel 6DMA Channel 7Each of the above list of DMA channel setting